{"id":16850,"date":"2021-08-12T10:06:29","date_gmt":"2021-08-12T10:06:29","guid":{"rendered":"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/"},"modified":"2026-02-23T15:39:56","modified_gmt":"2026-02-23T15:39:56","slug":"informe-de-uptime-institute-sobre-caidas-de-data-center-iv","status":"publish","type":"post","link":"https:\/\/pqc.es\/en\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/","title":{"rendered":"Informe de Uptime Institute sobre ca\u00eddas de data center (IV)"},"content":{"rendered":"<div class=\"news-content-block\">\n<p>Esas p&eacute;rdidas de alimentaci&oacute;n han sido, desde hace mucho tiempo, <strong>un aut&eacute;ntico azote para los gestores de los data centers<\/strong>, ya que se trata de un fen&oacute;meno llam&eacute;mosle &ldquo;binario&rdquo;, es decir, ON\/OFF, teniendo una repercusi&oacute;n inmediata en el servicio y, aunque el diagn&oacute;stico y resoluci&oacute;n puedan ser r&aacute;pidos, los sistemas IT pueden tardar horas en ser reestablecidos de una forma segura.<\/p>\n<p>Los porcentajes de ca&iacute;da de un data center por causa de la alimentaci&oacute;n el&eacute;ctrica van disminuyendo de una forma progresiva, pero siguen siendo un problema que <strong>s&oacute;lo puede ser prevenido mediante buenos dise&ntilde;os, procedimientos efectivos y un staff bien entrenado y experimentado.<\/strong><\/p>\n<h3>Dentro de lo puramente el&eacute;ctrico, las razones que la encuesta de Uptime Institute presenta como m&aacute;s habituales son las que se indican en el siguiente gr&aacute;fico:<\/h3>\n<\/div>\n<div class=\"news-image-block\">\n<figure class=\"media-holder\">\n            <img fetchpriority=\"high\" decoding=\"async\" alt=\"\" width=\"1280\" height=\"640\" src=\"\/wp-content\/uploads\/2021\/08\/image_427.jpg\" data-src-small=\"\/wp-content\/uploads\/2021\/08\/image_427.jpg\" data-src-medium=\"\/wp-content\/uploads\/2021\/08\/image_427.jpg\" data-src-large=\"\/wp-content\/uploads\/2021\/08\/image_427.jpg\" data-src-xlarge=\"\/wp-content\/uploads\/2021\/08\/image_427.jpg\" style=\"opacity: 1;\"><br \/>\n        <\/figure>\n<\/p><\/div>\n<div class=\"news-content-block\">\n<p>Hay que indicar que se daba opci&oacute;n a los encuestados a&nbsp;dar hasta un m&aacute;ximo de tres respuestas, por lo que la suma de porcentajes supera, por esa raz&oacute;n, el 100%.<\/p>\n<p>Resulta curioso observar c&oacute;mo, a pesar de todo lo que hemos padecido &uacute;ltimamente con asuntos relacionados con los grupos electr&oacute;genos, <strong>la palma se la llevan, un a&ntilde;o m&aacute;s, los fallos en los UPSs<\/strong>, lo cual no puede ser debido a otra cosa que, a la permanencia en los dise&ntilde;os de topolog&iacute;as muy simples, dado que, <strong>aunque no imposible, es francamente dif&iacute;cil encontrarse con escenarios donde fallen simult&aacute;neamente<\/strong> los UPSs de dos ramas independientes. Esto tiene pinta de que el paralelo redundante sigue, a&uacute;n, campando a sus anchas por muchos data centers.<\/p>\n<\/div>\n","protected":false},"excerpt":{"rendered":"<p>La ca\u00edda en la alimentaci\u00f3n el\u00e9ctrica. Otra consideraci\u00f3n m\u00e1s, que\u00a0describe las distintas causas por las que puede constituirse como origen de una ca\u00edda parcial o completa del sistema.<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[73],"tags":[],"class_list":["post-16850","post","type-post","status-publish","format-standard","hentry","category-data-center"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.2 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Informe de Uptime Institute sobre ca\u00eddas de data center (IV) | PQC<\/title>\n<meta name=\"description\" content=\"La ca\u00edda en la alimentaci\u00f3n el\u00e9ctrica. Otra consideraci\u00f3n m\u00e1s, que\u00a0describe las distintas causas por las que puede constituirse como origen de una ca\u00edda parcial o completa del sistema.\" \/>\n<meta name=\"robots\" content=\"noindex, follow\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Informe de Uptime Institute sobre ca\u00eddas de data center (IV) | PQC\" \/>\n<meta property=\"og:description\" content=\"La ca\u00edda en la alimentaci\u00f3n el\u00e9ctrica. Otra consideraci\u00f3n m\u00e1s, que\u00a0describe las distintas causas por las que puede constituirse como origen de una ca\u00edda parcial o completa del sistema.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/\" \/>\n<meta property=\"og:site_name\" content=\"PQC\" \/>\n<meta property=\"article:published_time\" content=\"2021-08-12T10:06:29+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2026-02-23T15:39:56+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/pqc.es\/wp-content\/uploads\/2026\/03\/IMAGEN_DEL_SITIO.png\" \/>\n\t<meta property=\"og:image:width\" content=\"1200\" \/>\n\t<meta property=\"og:image:height\" content=\"625\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/png\" \/>\n<meta name=\"author\" content=\"admin\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"admin\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"2 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/#article\",\"isPartOf\":{\"@id\":\"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/\"},\"author\":{\"name\":\"admin\",\"@id\":\"https:\/\/pqc.es\/#\/schema\/person\/66647e1005e9975e2dd2f7a1e9fa3ad6\"},\"headline\":\"Informe de Uptime Institute sobre ca\u00eddas de data center (IV)\",\"datePublished\":\"2021-08-12T10:06:29+00:00\",\"dateModified\":\"2026-02-23T15:39:56+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/\"},\"wordCount\":324,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\/\/pqc.es\/#organization\"},\"articleSection\":[\"Data Center\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/\",\"url\":\"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/\",\"name\":\"Informe de Uptime Institute sobre ca\u00eddas de data center (IV) | PQC\",\"isPartOf\":{\"@id\":\"https:\/\/pqc.es\/#website\"},\"datePublished\":\"2021-08-12T10:06:29+00:00\",\"dateModified\":\"2026-02-23T15:39:56+00:00\",\"description\":\"La ca\u00edda en la alimentaci\u00f3n el\u00e9ctrica. Otra consideraci\u00f3n m\u00e1s, que\u00a0describe las distintas causas por las que puede constituirse como origen de una ca\u00edda parcial o completa del sistema.\",\"breadcrumb\":{\"@id\":\"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Portada\",\"item\":\"https:\/\/pqc.es\/en\/home\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Informe de Uptime Institute sobre ca\u00eddas de data center (IV)\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/pqc.es\/#website\",\"url\":\"https:\/\/pqc.es\/\",\"name\":\"PQC\",\"description\":\"Consultor\u00eda, dise\u00f1o y operaci\u00f3n de Data Centers\",\"publisher\":{\"@id\":\"https:\/\/pqc.es\/#organization\"},\"alternateName\":\"PQC Data Centers\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/pqc.es\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Organization\",\"@id\":\"https:\/\/pqc.es\/#organization\",\"name\":\"PQC Data Centers\",\"alternateName\":\"PQC\",\"url\":\"https:\/\/pqc.es\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\/\/pqc.es\/#\/schema\/logo\/image\/\",\"url\":\"https:\/\/pqc.es\/wp-content\/uploads\/2026\/02\/LOGO-PQC.svg\",\"contentUrl\":\"https:\/\/pqc.es\/wp-content\/uploads\/2026\/02\/LOGO-PQC.svg\",\"width\":168,\"height\":40,\"caption\":\"PQC Data Centers\"},\"image\":{\"@id\":\"https:\/\/pqc.es\/#\/schema\/logo\/image\/\"},\"sameAs\":[\"https:\/\/www.linkedin.com\/company\/pqc\/posts\/?feedView=all\"]},{\"@type\":\"Person\",\"@id\":\"https:\/\/pqc.es\/#\/schema\/person\/66647e1005e9975e2dd2f7a1e9fa3ad6\",\"name\":\"admin\",\"sameAs\":[\"https:\/\/pqc.es\"]}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Informe de Uptime Institute sobre ca\u00eddas de data center (IV) | PQC","description":"La ca\u00edda en la alimentaci\u00f3n el\u00e9ctrica. Otra consideraci\u00f3n m\u00e1s, que\u00a0describe las distintas causas por las que puede constituirse como origen de una ca\u00edda parcial o completa del sistema.","robots":{"index":"noindex","follow":"follow"},"og_locale":"en_US","og_type":"article","og_title":"Informe de Uptime Institute sobre ca\u00eddas de data center (IV) | PQC","og_description":"La ca\u00edda en la alimentaci\u00f3n el\u00e9ctrica. Otra consideraci\u00f3n m\u00e1s, que\u00a0describe las distintas causas por las que puede constituirse como origen de una ca\u00edda parcial o completa del sistema.","og_url":"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/","og_site_name":"PQC","article_published_time":"2021-08-12T10:06:29+00:00","article_modified_time":"2026-02-23T15:39:56+00:00","og_image":[{"width":1200,"height":625,"url":"https:\/\/pqc.es\/wp-content\/uploads\/2026\/03\/IMAGEN_DEL_SITIO.png","type":"image\/png"}],"author":"admin","twitter_card":"summary_large_image","twitter_misc":{"Written by":"admin","Est. reading time":"2 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/#article","isPartOf":{"@id":"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/"},"author":{"name":"admin","@id":"https:\/\/pqc.es\/#\/schema\/person\/66647e1005e9975e2dd2f7a1e9fa3ad6"},"headline":"Informe de Uptime Institute sobre ca\u00eddas de data center (IV)","datePublished":"2021-08-12T10:06:29+00:00","dateModified":"2026-02-23T15:39:56+00:00","mainEntityOfPage":{"@id":"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/"},"wordCount":324,"commentCount":0,"publisher":{"@id":"https:\/\/pqc.es\/#organization"},"articleSection":["Data Center"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/","url":"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/","name":"Informe de Uptime Institute sobre ca\u00eddas de data center (IV) | PQC","isPartOf":{"@id":"https:\/\/pqc.es\/#website"},"datePublished":"2021-08-12T10:06:29+00:00","dateModified":"2026-02-23T15:39:56+00:00","description":"La ca\u00edda en la alimentaci\u00f3n el\u00e9ctrica. Otra consideraci\u00f3n m\u00e1s, que\u00a0describe las distintas causas por las que puede constituirse como origen de una ca\u00edda parcial o completa del sistema.","breadcrumb":{"@id":"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/pqc.es\/informe-de-uptime-institute-sobre-caidas-de-data-center-iv\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Portada","item":"https:\/\/pqc.es\/en\/home\/"},{"@type":"ListItem","position":2,"name":"Informe de Uptime Institute sobre ca\u00eddas de data center (IV)"}]},{"@type":"WebSite","@id":"https:\/\/pqc.es\/#website","url":"https:\/\/pqc.es\/","name":"PQC","description":"Consultor\u00eda, dise\u00f1o y operaci\u00f3n de Data Centers","publisher":{"@id":"https:\/\/pqc.es\/#organization"},"alternateName":"PQC Data Centers","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/pqc.es\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Organization","@id":"https:\/\/pqc.es\/#organization","name":"PQC Data Centers","alternateName":"PQC","url":"https:\/\/pqc.es\/","logo":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/pqc.es\/#\/schema\/logo\/image\/","url":"https:\/\/pqc.es\/wp-content\/uploads\/2026\/02\/LOGO-PQC.svg","contentUrl":"https:\/\/pqc.es\/wp-content\/uploads\/2026\/02\/LOGO-PQC.svg","width":168,"height":40,"caption":"PQC Data Centers"},"image":{"@id":"https:\/\/pqc.es\/#\/schema\/logo\/image\/"},"sameAs":["https:\/\/www.linkedin.com\/company\/pqc\/posts\/?feedView=all"]},{"@type":"Person","@id":"https:\/\/pqc.es\/#\/schema\/person\/66647e1005e9975e2dd2f7a1e9fa3ad6","name":"admin","sameAs":["https:\/\/pqc.es"]}]}},"_links":{"self":[{"href":"https:\/\/pqc.es\/en\/wp-json\/wp\/v2\/posts\/16850","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/pqc.es\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/pqc.es\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/pqc.es\/en\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/pqc.es\/en\/wp-json\/wp\/v2\/comments?post=16850"}],"version-history":[{"count":3,"href":"https:\/\/pqc.es\/en\/wp-json\/wp\/v2\/posts\/16850\/revisions"}],"predecessor-version":[{"id":18339,"href":"https:\/\/pqc.es\/en\/wp-json\/wp\/v2\/posts\/16850\/revisions\/18339"}],"wp:attachment":[{"href":"https:\/\/pqc.es\/en\/wp-json\/wp\/v2\/media?parent=16850"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/pqc.es\/en\/wp-json\/wp\/v2\/categories?post=16850"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/pqc.es\/en\/wp-json\/wp\/v2\/tags?post=16850"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}